Fehlercodes: E05_Mini_ECOi
Error in Indoor Unit Transmitting Signal to the Outdoor Unit
1. Error Detection Method
It is judged an error when a unit itself cannot receive a signal that it has sent.
- Indoor unit control PC board error
- The setting of the terminal resistor select switch on the outdoor unit main PC board is set incorrectly.
1 Indoor unit control PC board |
1-1 | Is the indoor/outdoor operation line connected to more than one outdoor unit? (Network wired?) | Yes | 1-2 | |
No | 1-3 | ||||
1-2 | Is the SHORT on the terminal resistor select switch on the outdoor main PC board set to one unit, and the others are OPEN? | Yes | 1-4 | ||
No | Set the SHORT to one unit only | ||||
1-3 | Is the terminal resistor select switch on the outdoor main PC board set to OPEN? | Yes | Make the SHORT setting | ||
No | 1-4 | ||||
1-4 | Is the indoor/outdoor operation line opened or shorted? | Yes | Correct the wiring | ||
No | 1-5 | ||||
1-5 | Replace the indoor unit control PC board. |
For information on the procedures for replacing the indoor unit’s control PC board, refer to the manual that is packaged withthe indoor unit service board.