Fehlercodes: L10_ECOi_ME1

 

Alarm Code L10
Alarm meaning Outdoor unit capacity not set
Alarm conditions The outdoor unit capacity has not been set, or the setting is not allowed by the system.
Probable cause This alarm occurs because the capacity has not been set.
Check If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it correctly. * After changing the setting, be sure to reset both the indoor and outdoor power.
Correction
  1. Connect the connector.
  2. Correct the connection at connector pins 4 and 5.
Example
Notes The outdoor unit maintenance remote controller is required in order to set the capacity in the outdoor unit EEPROM.