Fehlercodes: L10_ECOi_MF1
Alarm Code | L10 | |||
---|---|---|---|---|
Alarm meaning | Outdoor unit capacity not set | |||
Alarm conditions | This alarm occurs because the capacity has not been set. | |||
Probable cause | Incorrect outdoor system address settings | |||
Check | Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is not set to “0” or to a capacity that is not allowed. | |||
Correction | If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it correctly. * After changing the setting, be sure to reset both the indoor and outdoor power. |
|||
Example | – | |||
Notes | The outdoor unit maintenance remote controller is required in order to set the capacity in the outdoor unit EEPROM. |