Fehlercodes: P22_ECOi_ME1

Alarm Code P22
Alarm meaning Fan motor trouble.
Alarm conditions Fan motor start failure, fan motor Hall IC input failure.
Probable cause Possible causes are a Hall IC input circuit failure and a fan HIC failure.
Check

Check the fan motor wiring, the Hall IC wiring, and the connector connections.
If the wiring and connectors are normal, then check that the capacitor of the Hall IC input circuit is securely soldered on the outdoor unit control PCB. Also use a tester and measure the resistance between fan HIC power (HIC+) and ground (HIC–).
If there is a short-circuit, there is an HIC malfunction.

Correction

If the fan does not start, the below corrections may be effective.

  1. If there is a fan HIC failure or circuit failure, replace the PCB.
  2. If the fan motor is locked, replace the fan motor.
Example
Notes Turn OFF the power, and check the continuity of “+” and “–” on the fan circuit PCB.